Gratis · Rete e infrastruttura IT

Dimensionamento UPS.

Dimensiona un UPS per i tuoi apparati: potenza in VA e watt con margine, energia della batteria per l’autonomia desiderata, corrente e calore.

Prima di iniziare

Alcuni controlli tecnici sono in inglese. I testi Unicode sono supportati; formati e lingue di output dipendono dallo strumento.

I limiti tecnici sono indicati in inglese qui sotto. Controllali prima di elaborare file grandi o utilizzare il risultato.

CALCULATED IN YOUR BROWSER · NOTHING IS UPLOADED
Protected equipment

Modern power supplies with PFC are 0.9–0.99.

Check the UPS datasheet: many models are 0.9 or 1.0.

Lead-acid capacity falls at high discharge rates; lithium keeps more.

UPS size3,000 VA2,700 W at 0.9 PF
Load now
1,355 W · 1,506 VA
Minimum rating with headroom
2,258 VA / 2,032 W
Load on the chosen UPS
50.2 %
Battery energy for the runtime
470 Wh
Battery capacity at 48 V
9.8 Ah
Input current at full rating
13 A
Heat from equipment
4,623 BTU/h
UPS losses while online
≈ 151 W

  • Runtime from battery energy is approximate: lead-acid batteries deliver less at high loads (Peukert effect) and age. Check the manufacturer’s runtime chart for your load.
  • Measure real draw with a power meter or the PDU; nameplate ratings are maximums and often overstate typical use.
  • Laser printers and heaters have large surges and should not be on a UPS.

Come usare questo strumento: Dimensionamento UPS

Inserisci i dati o scegli il file. Regola le opzioni, genera il risultato e controllalo prima di copiarlo o scaricarlo.

Limiti e formati supportati

I dati vengono elaborati sul tuo dispositivo.

Note tecniche in inglese

Runtime from battery energy is approximate; check the manufacturer’s runtime chart. Standard sizes are common ratings, not specific products. Everything is calculated in your browser; nothing is sent or probed on the network.

Required rating = load × (1 + growth) ÷ maximum load, in both watts and VA; the smallest standard size meeting both is chosen. Battery energy = watts × runtime ÷ (inverter efficiency × usable capacity).

1,355 W of servers, storage, switch and firewall need a 3,000 VA / 2,700 W UPS and about 470 Wh of battery for 15 minutes.