Kostenlos · Netzwerk & IT-Infrastruktur
USV-Dimensionierung.
Dimensionieren Sie eine USV für Ihre Geräte: Leistung in VA und Watt mit Reserve, Batterieenergie für die gewünschte Laufzeit, Strom und Wärme.
Modern power supplies with PFC are 0.9–0.99.
Check the UPS datasheet: many models are 0.9 or 1.0.
Lead-acid capacity falls at high discharge rates; lithium keeps more.
- Load now
- 1,355 W · 1,506 VA
- Minimum rating with headroom
- 2,258 VA / 2,032 W
- Load on the chosen UPS
- 50.2 %
- Battery energy for the runtime
- 470 Wh
- Battery capacity at 48 V
- 9.8 Ah
- Input current at full rating
- 13 A
- Heat from equipment
- 4,623 BTU/h
- UPS losses while online
- ≈ 151 W
- Runtime from battery energy is approximate: lead-acid batteries deliver less at high loads (Peukert effect) and age. Check the manufacturer’s runtime chart for your load.
- Measure real draw with a power meter or the PDU; nameplate ratings are maximums and often overstate typical use.
- Laser printers and heaters have large surges and should not be on a UPS.
So verwenden Sie das Tool: USV-Dimensionierung
Geben Sie Daten ein oder wählen Sie eine Datei. Passen Sie die Einstellungen an, erstellen Sie das Ergebnis und prüfen Sie es vor dem Kopieren oder Herunterladen.
Grenzen und unterstützte Formate
Ihre Eingaben werden auf Ihrem Gerät verarbeitet.
Technische Hinweise auf Englisch
Runtime from battery energy is approximate; check the manufacturer’s runtime chart. Standard sizes are common ratings, not specific products. Everything is calculated in your browser; nothing is sent or probed on the network.
Required rating = load × (1 + growth) ÷ maximum load, in both watts and VA; the smallest standard size meeting both is chosen. Battery energy = watts × runtime ÷ (inverter efficiency × usable capacity).
1,355 W of servers, storage, switch and firewall need a 3,000 VA / 2,700 W UPS and about 470 Wh of battery for 15 minutes.