免费 · 网络与 IT 基础设施

UPS 容量计算器.

根据设备估算 UPS 容量:含余量的 VA 和瓦特额定值、所需续航的电池能量、电流和发热量。

开始之前

部分技术控件使用英语。支持 Unicode 文本;文件格式和输出语言取决于具体工具。

下面以英语列出技术限制。处理大型文件或使用结果之前,请先查看这些限制。

CALCULATED IN YOUR BROWSER · NOTHING IS UPLOADED
Protected equipment

Modern power supplies with PFC are 0.9–0.99.

Check the UPS datasheet: many models are 0.9 or 1.0.

Lead-acid capacity falls at high discharge rates; lithium keeps more.

UPS size3,000 VA2,700 W at 0.9 PF
Load now
1,355 W · 1,506 VA
Minimum rating with headroom
2,258 VA / 2,032 W
Load on the chosen UPS
50.2 %
Battery energy for the runtime
470 Wh
Battery capacity at 48 V
9.8 Ah
Input current at full rating
13 A
Heat from equipment
4,623 BTU/h
UPS losses while online
≈ 151 W

  • Runtime from battery energy is approximate: lead-acid batteries deliver less at high loads (Peukert effect) and age. Check the manufacturer’s runtime chart for your load.
  • Measure real draw with a power meter or the PDU; nameplate ratings are maximums and often overstate typical use.
  • Laser printers and heaters have large surges and should not be on a UPS.

使用方法: UPS 容量计算器

输入数据或选择文件,调整设置并生成结果。复制或下载之前,请检查结果。

限制与支持格式

输入内容在您的设备上处理。

英语技术说明

Runtime from battery energy is approximate; check the manufacturer’s runtime chart. Standard sizes are common ratings, not specific products. Everything is calculated in your browser; nothing is sent or probed on the network.

Required rating = load × (1 + growth) ÷ maximum load, in both watts and VA; the smallest standard size meeting both is chosen. Battery energy = watts × runtime ÷ (inverter efficiency × usable capacity).

1,355 W of servers, storage, switch and firewall need a 3,000 VA / 2,700 W UPS and about 470 Wh of battery for 15 minutes.