Gratis · Netwerk en IT-infrastructuur
UPS-dimensionering.
Dimensioneer een UPS voor uw apparatuur: VA- en wattvermogen met marge, batterij-energie voor de gewenste looptijd, stroom en warmte.
Modern power supplies with PFC are 0.9–0.99.
Check the UPS datasheet: many models are 0.9 or 1.0.
Lead-acid capacity falls at high discharge rates; lithium keeps more.
- Load now
- 1,355 W · 1,506 VA
- Minimum rating with headroom
- 2,258 VA / 2,032 W
- Load on the chosen UPS
- 50.2 %
- Battery energy for the runtime
- 470 Wh
- Battery capacity at 48 V
- 9.8 Ah
- Input current at full rating
- 13 A
- Heat from equipment
- 4,623 BTU/h
- UPS losses while online
- ≈ 151 W
- Runtime from battery energy is approximate: lead-acid batteries deliver less at high loads (Peukert effect) and age. Check the manufacturer’s runtime chart for your load.
- Measure real draw with a power meter or the PDU; nameplate ratings are maximums and often overstate typical use.
- Laser printers and heaters have large surges and should not be on a UPS.
Zo gebruik je deze tool: UPS-dimensionering
Voer gegevens in of kies een bestand. Pas de instellingen aan, maak het resultaat en controleer het voordat je het kopieert of downloadt.
Limieten en ondersteunde formaten
Je invoer wordt op je apparaat verwerkt.
Technische opmerkingen in het Engels
Runtime from battery energy is approximate; check the manufacturer’s runtime chart. Standard sizes are common ratings, not specific products. Everything is calculated in your browser; nothing is sent or probed on the network.
Required rating = load × (1 + growth) ÷ maximum load, in both watts and VA; the smallest standard size meeting both is chosen. Battery energy = watts × runtime ÷ (inverter efficiency × usable capacity).
1,355 W of servers, storage, switch and firewall need a 3,000 VA / 2,700 W UPS and about 470 Wh of battery for 15 minutes.