PasteZap
🌐 English
Free · No account

FREE · NETWORK & IT INFRASTRUCTURE

Server Rack Planner.

Plan rack space, power and cooling: rack units, racks needed, kW per rack, circuits for A+B feeds, BTU/h and weight.

Limits & supported formats

Watts as entered; electrical codes differ by country and final designs need a qualified electrician. Weight uses the rack’s static rating. Everything is calculated in your browser; nothing is sent or probed on the network.

CALCULATED IN YOUR BROWSER · NOTHING IS UPLOADED
Equipment
Racks239 U of 66 U usable
Power per rack
4.33 kW
Total power
8.65 kW
Heat to remove
29,514 BTU/h · 2.46 tons
Circuit capacity
2.94 kW (1-phase 16 A)
Circuits per rack
4 (A + B)
Current per rack
18.8 A
Weight per rack
222 kg

Equipment

EquipmentQtySpacePowerWeight
1U servers1010 U3,500 W160 kg
2U servers612 U3,600 W168 kg
Storage array14 U900 W45 kg
Top-of-rack switches22 U500 W16 kg
Patch panels44 U0 W8 kg
Cable managers44 U0 W6 kg
UPS13 U150 W40 kg
  • Power uses watts as entered; measured draw is usually well below nameplate. Three-phase power assumes balanced phases and unity power factor.
  • Electrical codes differ by country (continuous-load derating, breaker types). Have the final design checked by a qualified electrician.

How to use Server Rack Planner

List equipment with quantity, height, watts and weight, then pick the rack height, reserve, power feed and breaker.

How it works

Racks = total U ÷ usable U per rack (and weight ÷ rating); circuit capacity = voltage × current × derating (× √3 for three phase); heat = watts × 3.412 BTU/h.

Example

28 devices filling 39 U in 42U racks with 20 % reserve need 2 racks of 4.3 kW each, two 16 A circuits per feed (A + B) and about 29,500 BTU/h of cooling.

Questions about Server Rack Planner

Is Server Rack Planner free, and do I need an account?

Yes. This tool is free to use in your browser without an account. Processing takes place on your device.

What are the limits and what should I check?

Watts as entered; electrical codes differ by country and final designs need a qualified electrician. Weight uses the rack’s static rating. Everything is calculated in your browser; nothing is sent or probed on the network. Review the result before using it in your work.

Is my input sent to a server?

Your input is processed in your browser and is not uploaded by this tool. Files and pasted text are cleared when the page is refreshed. Normal website requests are still required to load the page and its libraries. Read the privacy explanation.