Kostenlos · Netzwerk & IT-Infrastruktur
Serverrack-Planer.
Planen Sie Platz, Strom und Kühlung: Höheneinheiten, Anzahl Racks, kW pro Rack, A+B-Stromkreise, BTU/h und Gewicht.
- Power per rack
- 4.33 kW
- Total power
- 8.65 kW
- Heat to remove
- 29,514 BTU/h · 2.46 tons
- Circuit capacity
- 2.94 kW (1-phase 16 A)
- Circuits per rack
- 4 (A + B)
- Current per rack
- 18.8 A
- Weight per rack
- 222 kg
Equipment
| Equipment | Qty | Space | Power | Weight |
|---|---|---|---|---|
| 1U servers | 10 | 10 U | 3,500 W | 160 kg |
| 2U servers | 6 | 12 U | 3,600 W | 168 kg |
| Storage array | 1 | 4 U | 900 W | 45 kg |
| Top-of-rack switches | 2 | 2 U | 500 W | 16 kg |
| Patch panels | 4 | 4 U | 0 W | 8 kg |
| Cable managers | 4 | 4 U | 0 W | 6 kg |
| UPS | 1 | 3 U | 150 W | 40 kg |
- Power uses watts as entered; measured draw is usually well below nameplate. Three-phase power assumes balanced phases and unity power factor.
- Electrical codes differ by country (continuous-load derating, breaker types). Have the final design checked by a qualified electrician.
So verwenden Sie das Tool: Serverrack-Planer
Geben Sie Daten ein oder wählen Sie eine Datei. Passen Sie die Einstellungen an, erstellen Sie das Ergebnis und prüfen Sie es vor dem Kopieren oder Herunterladen.
Grenzen und unterstützte Formate
Ihre Eingaben werden auf Ihrem Gerät verarbeitet.
Technische Hinweise auf Englisch
Watts as entered; electrical codes differ by country and final designs need a qualified electrician. Weight uses the rack’s static rating. Everything is calculated in your browser; nothing is sent or probed on the network.
Racks = total U ÷ usable U per rack (and weight ÷ rating); circuit capacity = voltage × current × derating (× √3 for three phase); heat = watts × 3.412 BTU/h.
28 devices filling 39 U in 42U racks with 20 % reserve need 2 racks of 4.3 kW each, two 16 A circuits per feed (A + B) and about 29,500 BTU/h of cooling.