PasteZap
🌐 简体中文
免费 · 无需注册

免费 · 网络与 IT 基础设施

服务器机柜规划器.

规划空间、供电和制冷:机架单位、机柜数量、每柜功率、A+B 双路电源、BTU/h 和重量。

开始之前

部分技术控件使用英语。支持 Unicode 文本;文件格式和输出语言取决于具体工具。

下面以英语列出技术限制。处理大型文件或使用结果之前,请先查看这些限制。

CALCULATED IN YOUR BROWSER · NOTHING IS UPLOADED
Equipment
Racks239 U of 66 U usable
Power per rack
4.33 kW
Total power
8.65 kW
Heat to remove
29,514 BTU/h · 2.46 tons
Circuit capacity
2.94 kW (1-phase 16 A)
Circuits per rack
4 (A + B)
Current per rack
18.8 A
Weight per rack
222 kg

Equipment

EquipmentQtySpacePowerWeight
1U servers1010 U3,500 W160 kg
2U servers612 U3,600 W168 kg
Storage array14 U900 W45 kg
Top-of-rack switches22 U500 W16 kg
Patch panels44 U0 W8 kg
Cable managers44 U0 W6 kg
UPS13 U150 W40 kg
  • Power uses watts as entered; measured draw is usually well below nameplate. Three-phase power assumes balanced phases and unity power factor.
  • Electrical codes differ by country (continuous-load derating, breaker types). Have the final design checked by a qualified electrician.

使用方法: 服务器机柜规划器

输入数据或选择文件,调整设置并生成结果。复制或下载之前,请检查结果。

限制与支持格式

输入内容在您的设备上处理。

英语技术说明

Watts as entered; electrical codes differ by country and final designs need a qualified electrician. Weight uses the rack’s static rating. Everything is calculated in your browser; nothing is sent or probed on the network.

Racks = total U ÷ usable U per rack (and weight ÷ rating); circuit capacity = voltage × current × derating (× √3 for three phase); heat = watts × 3.412 BTU/h.

28 devices filling 39 U in 42U racks with 20 % reserve need 2 racks of 4.3 kW each, two 16 A circuits per feed (A + B) and about 29,500 BTU/h of cooling.